Open the electrical drawings of any building in the Middle East or Africa and you will see the same abbreviations: MDB, SMDB, DB, MCC, ATS, PFC. They describe a chain that carries power from the transformer to every socket, light and motor. Knowing what each link does makes it easier to read a single-line diagram, compare offers and avoid buying the wrong board for the job.
The distribution chain
Power usually arrives from a transformer or the utility's low-voltage supply, with a generator as backup. From there it is split in stages, and each stage is a board:
- MDB, the main distribution board, takes the full supply and feeds the large loads and the sub-main boards.
- SMDB, the sub-main distribution board, serves one floor, one wing or one plant area.
- DB, the final distribution board, feeds the final circuits: lighting, sockets and small equipment.
Next to this chain sit special-purpose boards: the MCC for motors, the ATS panel for changeover to the generator and the PFC panel for power factor correction.
MDB: main distribution board
The MDB is the largest board in the building. Its incomer is usually an air circuit breaker (ACB) rated for the transformer's full-load current, often from 1,000 A to several thousand amperes. Its outgoing feeders are moulded-case circuit breakers (MCCB), and on large sites ACBs as well.
Because it sits closest to the transformer, the MDB faces the highest short-circuit current. Its short-circuit rating (for example 50 kA for 1 s) and its form of internal separation are the two figures that drive its size and cost. Our guide to forms of separation explains the second.
SMDB: sub-main distribution board
An SMDB receives one feeder from the MDB and splits it again. Typical ratings run from 100 A to 800 A, with an MCCB or a switch-disconnector as incomer and MCCBs as outgoing feeders. The fault level is lower than at the MDB, because the cable between the two limits it, but it must still be calculated, not assumed.
SMDBs often sit in plant rooms, car parks or industrial areas, so their IP rating matters more than the MDB's.
DB: final distribution board
The DB is the board most people have seen: rows of miniature circuit breakers (MCB), residual current devices (RCD or RCBO) for socket circuits, and a main switch or small MCCB as incomer. DBs are sized by the number of ways, the number of outgoing single-pole positions per phase. A "TPN 12-way" board is a three-phase-and-neutral board with twelve ways per phase.
In apartments and offices, the DB often includes the energy meter, or sits next to a meter panel.
MCC, ATS and PFC panels
| Board | What it does | Typical content |
|---|---|---|
| MCC (motor control centre) | Starts, stops and protects motors: pumps, fans, compressors, conveyors | Motor starters (direct-on-line, star-delta, soft starters, variable speed drives), overload relays, control circuits |
| ATS panel (automatic transfer switch) | Switches the load from the utility to the generator and back | Two interlocked breakers or a transfer switch, a controller, voltage monitoring |
| PFC panel (capacitor bank) | Corrects the power factor to avoid utility penalties and free capacity | Capacitor steps, contactors, detuning reactors where harmonics are present, a power factor controller |
| ESMDB (emergency SMDB) | Feeds life-safety loads from the generator side: fire pumps, emergency lighting, lifts | As an SMDB, supplied from the essential bus |
Side by side
| MDB | SMDB | DB | |
|---|---|---|---|
| Fed from | Transformer or utility | MDB | SMDB or MDB |
| Typical incomer | ACB | MCCB or switch-disconnector | MCB, main switch or small MCCB |
| Typical outgoing | MCCB, ACB | MCCB | MCB, RCBO |
| Typical current | 1,000 A and up | 100 A to 800 A | Up to about 250 A |
| Fault level | Highest | Medium | Lowest |
| Standard | IEC 61439-2 | IEC 61439-2 | IEC 61439-3 when operated by ordinary persons, otherwise IEC 61439-2 |
The ranges are typical, not fixed. A small building may have no SMDB at all; a large hospital may have three levels of sub-main boards.
What to give your panel builder
For every board on the single-line diagram, the panel builder needs the incomer rating, the list of outgoing feeders with their ratings, the short-circuit level at that point, the IP code, the form of separation, the installation (floor-standing or wall-mounted, indoor or outdoor) and the cable entry. Our switchboard RFQ checklist covers the full list.
SEGA M boards for each level
- MDB: SIVACON S8, built by SEGA M as a Siemens Advanced Partner, up to 7,010 A and 150 kA for 1 s; or our own SG-1 switchgear up to 4,000 A, which is also used for MCC, PFC and ATS boards.
- SMDB: the type-tested MFB load centre, 250 A or 400 A, 36 kA for 1 s, 4 to 10 MCCB feeders, up to IP65.
- DB: the type-tested NSFB fishbone board, 160 A busbar, 16 kA for 1 s, 12 to 60 MCB ways, and meter panels for residential buildings such as the 24-line panel with meter.
Send us your single-line diagram and we will propose the boards for every level, in one offer from one factory.
Frequently asked questions
What is the difference between an MDB and an SMDB?
The MDB takes the full supply from the transformer and feeds the building. An SMDB takes one feeder from the MDB and distributes it to one area. The MDB has a larger rating and a higher short-circuit level.
What does "ways" mean on a distribution board?
The number of outgoing single-pole positions per phase. A TPN 12-way board has twelve positions on each of its three phases.
Which standard applies to distribution boards?
IEC 61439-2 for power switchgear assemblies such as MDBs, SMDBs and MCCs. Small boards that ordinary persons may operate, such as final DBs in homes and offices, fall under IEC 61439-3.
Can one manufacturer supply all the boards of a project?