How Many Ways? Sizing a Distribution Board: 12, 18, 24 or 36 Lines

Switchboards

How Many Ways? Sizing a Distribution Board: 12, 18, 24 or 36 Lines

The most common question about a distribution board is "how many lines?". Here is how to count the circuits, how much spare to keep, and which board size fits an apartment, a villa or a shop.

SEGA M Engineering Team
Updated 14 Nov 20266 min read
SEGA M metal distribution board enclosure

"How many lines do I need?" is the first question every electrician and buyer asks about a distribution board. Choose too few and the board is full on day one; choose too many and you pay for empty space. The answer comes from a simple count of circuits, a decision on single-phase or three-phase supply, and a sensible margin for the future.

What "ways" or "lines" means

A way (often called a line) is one outgoing position for a single-pole circuit breaker. A 24-way single-phase board holds 24 single-pole MCBs. A three-phase board is described per phase: a "TPN 12-way" board has 12 ways on each of L1, L2 and L3, so 36 single-pole positions in total. A two-pole or three-pole breaker takes two or three ways.

Step 1: count the circuits

Each of these normally has its own breaker:

  • Lighting: one circuit per floor or zone, often two or three in an apartment.
  • Socket outlets: one circuit per room or group of rooms; separate circuits for the kitchen.
  • Air conditioners: one circuit for each split unit. Larger units may need a two-pole or three-pole breaker.
  • Water heater, cooker, washing machine, dishwasher: one circuit each.
  • Pumps, gate motors, lifts, outdoor lighting: one circuit each, often three-phase.
  • Main or group residual current devices: they take ways too, usually two (single-phase) or four (three-phase).

Step 2: add spare capacity

Add 20 to 30 % spare ways. New air conditioners, a second water heater, a solar inverter or an EV charger are typical additions in the life of a building. A board with no free ways forces an extra box beside it later, which is more expensive and less safe than buying the right size now.

Step 3: single-phase or three-phase

Smaller apartments are usually supplied single-phase. Larger apartments, villas, shops with heavy air-conditioning and most offices are supplied three-phase, and the load is spread across the three phases. On a three-phase board, plan the circuit schedule so that large loads such as air conditioners and water heaters are split between L1, L2 and L3.

Typical sizes

UseTypical circuitsBoard to consider
Studio or small apartment6 to 912 ways
Two or three-bedroom apartment10 to 1418 ways
Large apartment or small villa15 to 2024 ways
Villa, shop or small office with several AC units20 to 2836 ways, or three-phase
Office floor, clinic, restaurant30 and moreThree-phase board, or a fishbone board with 36 to 60 ways

These are starting points. Always size from your own circuit list and spare margin.

Boards with a meter

In apartments and shops, the board often has to hold the electricity meter too. A board with meter space keeps the meter and the circuit breakers in one enclosure, which saves wall space and installation time. Check whether the meter is single-phase (220 V) or three-phase (380 V), and whether the utility requires a specific meter type, such as an electronic prepaid card meter.

Other details to check

  • Mounting: flush (recessed in the wall) or surface, and the wall depth available.
  • Incomer: main switch or MCB, and its rating.
  • Enclosure: metal or plastic, colour, IP rating for wet or dusty places.
  • Labels: a circuit chart inside the door saves time at every fault.

Distribution boards from SEGA M

SEGA M manufactures distribution boards in Egypt in 12, 18, 24 and 36-line versions, horizontal and vertical, with or without a built-in meter. The 24-line panel with kWh meter (485 x 350 x 90 mm) suits large apartments, villas and shops; the 12/24-line modern panel (380 x 350 x 90 mm) lets you increase the number of MCBs by omitting the incomer section; and the 36-line panel with meter covers bigger units. Datasheets for each model are on the product pages.

Need only a few boards for a home or shop in Egypt? Order them online from the SEGA M Shop. For projects and export, send us your circuit schedule and we will propose the board for every unit.

Frequently asked questions

What does a 24-line distribution board mean?

It has 24 positions for single-pole circuit breakers. Two-pole and three-pole breakers take two or three of those positions.

How many ways does an apartment need?

Count one way per circuit (lighting, sockets, each air conditioner, water heater, kitchen appliances), then add 20 to 30 % spare. Most two or three-bedroom apartments end up with an 18 or 24-way board.

Should I choose a single-phase or three-phase board?

It follows the supply from the utility. Large apartments, villas, shops with several air conditioners and offices are usually three-phase.

Can the meter go in the same board?

Yes. Boards with meter space hold the electricity meter and the circuit breakers in one enclosure.